Fire Pump vs Jockey Pump: What’s the Difference?

Purpose

Overview of Fire Protection System

A fire protection system is a comprehensive network designed to detect, control, and extinguish fires to safeguard lives and property. Within this system, two essential components are the fire pump and the jockey pump, each serving distinct functions to ensure the system’s effectiveness and reliability.

Fire Pump

The primary purpose of a fire pump is to deliver high-pressure, high-capacity water flow during fire emergencies. This ensures that firefighting equipment, such as sprinklers, fire hydrants, and hoses, receive an adequate water supply to effectively combat fires. The fire pump activates automatically when the system detects a significant drop in pressure, typically caused by the activation of firefighting devices.

Practical Applications

  • Commercial Buildings: In high-rise office buildings, fire pumps provide the necessary pressure to deliver water to upper floors, ensuring that sprinklers and fire hoses are effective throughout the building.
  • Industrial Facilities: Factories and warehouses often have fire pumps to maintain a robust water supply for extensive sprinkler systems, crucial for protecting large areas filled with valuable equipment and materials.
  • Residential Complexes: In large apartment complexes, fire pumps ensure that water reaches all units quickly during an emergency, enhancing the safety of residents.

Effectiveness

Statistics show that buildings equipped with fire pumps can significantly reduce fire damage. For instance, a study by the National Fire Protection Association (NFPA) found that buildings with properly maintained fire pumps experienced 50% less fire damage compared to those without.

Jockey Pump

The jockey pump maintains steady system pressure during non-emergency conditions. It compensates for minor pressure losses due to leaks, temperature fluctuations, or other factors. By maintaining consistent pressure, the jockey pump prevents the fire pump from activating unnecessarily, reducing wear and tear and conserving energy.

Practical Applications

  • Hospitals: In healthcare facilities, jockey pumps ensure that the fire protection system remains pressurized, ready to respond without delay, which is critical for patient safety.
  • Data Centers: These facilities require constant pressure maintenance to protect sensitive equipment from potential fire damage. Jockey pumps help maintain the integrity of the fire protection system without unnecessary fire pump activation.
  • Shopping Malls: Large commercial spaces benefit from jockey pumps that keep the system ready at all times, ensuring quick response in case of a fire.

Preventing Unnecessary Activation

Examples show that jockey pumps can prevent unnecessary fire pump activation. For instance, in a university campus, the installation of jockey pumps reduced false activations of the main fire pump by 70%, thereby extending the life of the equipment and reducing maintenance costs.

Key Differences in Purpose

  • Fire Pump: Designed for high-pressure, high-capacity water flow during emergencies, ensuring effective firefighting capabilities.
  • Jockey Pump: Maintains steady system pressure during normal conditions, preventing unnecessary activation of the fire pump and ensuring system readiness.

Importance in Fire Protection Systems

Both the fire pump and jockey pump are integral components of a fire protection system, each serving distinct but complementary purposes. The fire pump’s ability to deliver a large volume of water under high pressure is critical for effective fire suppression during emergencies. Meanwhile, the jockey pump’s role in maintaining system pressure ensures that the fire protection system remains in optimal condition, ready to respond instantly when needed. Together, these pumps ensure that the fire protection system operates efficiently, providing reliable protection against fire hazards.

Visual Aid

Fire Protection System Diagram
Diagram showing the fire protection system with labeled fire pumps and jockey pumps, illustrating their respective roles and connections.

Fire Pump and Jockey Pump Operation

Fire pumps and jockey pumps are essential components of fire protection systems, ensuring a reliable water supply during emergencies. Fire pumps deliver high-pressure water to fire suppression systems, while jockey pumps maintain system pressure to prevent unnecessary activation of the fire pump.

Introduction

Fire pumps and jockey pumps play critical roles in maintaining the readiness and effectiveness of fire protection systems. Fire pumps activate during emergencies to provide the necessary water pressure for firefighting, whereas jockey pumps operate intermittently to maintain consistent system pressure.

Fire Pump Operation

Fire pumps are designed to operate in emergency situations, delivering a high volume of water at a high pressure to fire suppression systems like sprinklers and hydrants. They are typically triggered by a significant drop in system pressure, which can occur when firefighting devices are activated.

Automatic Activation

Fire pumps are equipped with automatic controls that detect pressure drops and activate the pump without manual intervention. For instance, if a sprinkler head activates due to a fire, the resulting pressure drop triggers the fire pump to start.

  • Pressure Switches: These devices monitor the system pressure. When the pressure falls below a preset level, they send a signal to start the fire pump.
  • Control Panels: The control panel manages the operation of the fire pump, including starting, stopping, and monitoring its status. It may include manual overrides for testing and maintenance purposes.

Manual Operation

Manual controls are necessary even with automatic systems for situations like system testing or maintenance. For example, during a weekly test, a technician might manually start the pump using the control panel to ensure it operates correctly.

Jockey Pump Operation

Jockey pumps operate intermittently to maintain consistent system pressure, preventing the main fire pump from activating unnecessarily. They are controlled by pressure switches and controllers that start and stop the pump based on the system’s pressure levels.

Pressure Maintenance

Jockey pumps compensate for minor pressure losses in the system due to leaks, temperature fluctuations, or other factors. By maintaining steady pressure, they ensure that the fire protection system remains ready to respond instantly during an emergency.

  • Pressure Switches: Similar to those used in fire pumps, these switches monitor the system pressure and activate the jockey pump when the pressure falls below a certain threshold.
  • Controllers: These devices manage the jockey pump’s operation, ensuring it starts and stops as needed to maintain the desired pressure level.

Testing and Maintenance

Regular testing and maintenance are crucial to ensure the fire pump and jockey pump operate correctly when needed. Neglecting this can lead to system failures during emergencies.

  • Weekly Testing: Conducting weekly tests to verify the pump’s readiness and proper function. For example, a technician might manually start the pump and check for any issues.
  • Annual Inspections: Performing comprehensive inspections and maintenance at least once a year, as recommended by the NFPA and other relevant standards. Studies show that well-maintained systems significantly improve response times and effectiveness during fire emergencies.

Key Differences in Operation

  • Fire Pump: Operates during emergencies or system tests, providing high-pressure water flow. It is not meant for frequent or continuous operation.
  • Jockey Pump: Operates intermittently to maintain system pressure, controlled by pressure switches and controllers. It ensures the system remains pressurized and ready without unnecessary fire pump activation.

Importance of Proper Operation

Ensuring that both fire pumps and jockey pumps operate correctly is vital for the effectiveness of a fire protection system. Proper operation and regular maintenance guarantee that the system responds promptly and efficiently during emergencies, providing reliable protection against fire hazards. Regular testing and maintenance also help in identifying and resolving issues before they lead to system failures, thereby ensuring the continuous readiness of the fire protection system.

Capacity and Size

Fire Pump Capacity and Size

Fire pumps are essential for delivering high volumes of water at high pressure to meet the demands of firefighting systems during emergencies. The capacity and size of fire pumps are critical factors that determine their effectiveness in delivering the necessary water flow and pressure.

Capacity

The capacity of a fire pump refers to the volume of water it can deliver, usually measured in gallons per minute (GPM) or liters per minute (LPM). Fire pumps are available in various capacities to suit different building requirements and fire protection needs.

  • Small Buildings: For small buildings, such as residential complexes or small commercial properties, fire pumps with capacities ranging from 500 to 750 GPM are typically sufficient.
  • Medium to Large Buildings: Medium to large buildings, including shopping malls and office buildings, often require fire pumps with capacities between 1,000 and 2,000 GPM to ensure adequate coverage.
  • High-Rise and Industrial Facilities: High-rise buildings and industrial facilities, such as factories and warehouses, may necessitate fire pumps with capacities ranging from 2,500 to 5,000 GPM or more to meet the extensive water supply needs.

The required capacity is determined based on the building’s size, occupancy, and fire hazard classification. For example, a high-rise office building with multiple floors and extensive sprinkler systems would require a higher capacity pump compared to a smaller, single-story building.

Size

The size of a fire pump is influenced by its capacity and the pressure it needs to generate. Larger capacity pumps are physically bigger and require more space for installation. Factors affecting the size of a fire pump include:

  • Pump Type: Horizontal split-case pumps are often used in large installations due to their high efficiency and reliability. Vertical in-line pumps are more compact and suitable for buildings with space constraints. Vertical turbine pumps are ideal for applications requiring high pressure and are often used in high-rise buildings.
  • Power Source: Electric motor-driven pumps are generally more compact than diesel engine-driven pumps. Diesel pumps, while larger, are used where reliable electric power may not be available during an emergency.
  • Installation Space: Adequate space must be provided for maintenance and operation, including clearances around the pump. In buildings with limited space, vertical in-line pumps are often preferred for their smaller footprint.

Jockey Pump Capacity and Size

Jockey pumps, also known as pressure maintenance pumps, are designed to maintain the pressure in the fire protection system during non-emergency conditions. Their capacity and size are significantly smaller compared to fire pumps, reflecting their role in handling minor pressure fluctuations rather than large-scale water delivery.

Capacity

The capacity of a jockey pump is typically much lower than that of a fire pump, as it only needs to compensate for minor pressure losses.

  • Small Systems: For small fire protection systems, jockey pumps with capacities ranging from 10 to 20 GPM are generally adequate.
  • Medium Systems: Medium-sized systems may require jockey pumps with capacities between 20 and 50 GPM.
  • Large Systems: Large systems, such as those in industrial facilities, might necessitate jockey pumps with capacities ranging from 50 to 100 GPM.

The capacity of a jockey pump is selected based on the system’s pressure maintenance needs, ensuring that it can effectively manage leaks, temperature changes, and other minor pressure variations without overloading the system.

Size

Jockey pumps are compact and designed for continuous or intermittent operation. Factors affecting the size of a jockey pump include:

  • Pump Type: Multi-stage centrifugal pumps are commonly used for jockey pumps due to their efficiency and compact design. These pumps are effective in maintaining system pressure with minimal space requirements.
  • Installation Space: Jockey pumps require minimal space and can often be installed adjacent to the fire pump or within the same pump room. This allows for easy integration into existing fire protection systems.
  • Pressure Rating: The size may vary slightly based on the pressure rating required to maintain the system pressure effectively. Higher pressure ratings might require slightly larger pumps, but they remain relatively small compared to fire pumps.

Comparative Overview

  • Fire Pump:
    • Capacity: High (500-5,000+ GPM)
    • Size: Large, requiring significant installation space
  • Jockey Pump:
    • Capacity: Low (10-100 GPM)
    • Size: Compact, requiring minimal installation space

Understanding the capacity and size differences between fire pumps and jockey pumps is essential for designing an effective fire protection system. Fire pumps provide the necessary water flow and pressure during emergencies, while jockey pumps ensure the system remains pressurized and ready for immediate activation. Proper selection and sizing of both pumps are crucial to maintaining the reliability and efficiency of the fire protection system.

Control Mechanisms

Fire protection systems rely on sophisticated control mechanisms to ensure the effective operation of fire pumps and jockey pumps. These control mechanisms automatically manage the activation and operation of the pumps, maintaining system pressure and ensuring readiness during emergencies.

Fire Pump Control Mechanisms

Fire pumps are critical components activated during fire emergencies to deliver high-pressure water. Their control mechanisms ensure they operate effectively when needed.

Automatic Controls

Automatic controls are essential for fire pump operation, allowing the system to respond instantly to emergencies without manual intervention.

  • Pressure Switches: These switches monitor the system’s pressure levels. When a significant drop in pressure is detected, such as when a sprinkler or hydrant is activated, the pressure switches send a signal to start the fire pump. For example, in a high-rise building, a pressure switch might trigger the fire pump when a sprinkler on the 10th floor is activated due to a fire.
  • Control Panels: The control panel serves as the brain of the fire pump system. It manages the starting, stopping, and monitoring of the fire pump. The control panel includes various indicators and alarms to notify operators of the pump’s status and any potential issues. These panels can show real-time data, such as pump pressure and flow rates, ensuring operators are well-informed.
  • Flow Switches: Installed in the piping system, flow switches detect water movement, indicating the activation of firefighting equipment. When flow is detected, they can trigger the fire pump to ensure adequate water supply. For instance, if a sprinkler system in a warehouse is activated, the flow switch detects the water movement and signals the fire pump to start.

Manual Controls

Manual controls are necessary for testing, maintenance, and emergency situations where automatic controls might fail.

  • Manual Start/Stop: Fire pumps are equipped with manual start and stop buttons on the control panel. These controls allow operators to manually activate or deactivate the pump during routine tests or maintenance activities. Regular testing ensures the pump’s readiness, such as monthly operational tests to verify its functionality.
  • Emergency Overrides: In case of automatic system failure, emergency override controls enable operators to manually control the fire pump, ensuring that water supply is maintained during critical situations. This ensures that the fire protection system remains operational even if the primary controls are compromised.

Jockey Pump Control Mechanisms

Jockey pumps maintain consistent pressure in the fire protection system during non-emergency conditions, preventing unnecessary activation of the main fire pump. Their control mechanisms ensure precise pressure maintenance.

Pressure Maintenance Controls

Jockey pumps are controlled by mechanisms designed to maintain system pressure within a specified range.

  • Pressure Switches: Similar to those used in fire pumps, pressure switches for jockey pumps monitor the system pressure. When the pressure falls below a predetermined threshold, the switches activate the jockey pump to restore the pressure. This is crucial in maintaining system readiness without triggering the main fire pump.
  • Pressure Relief Valves: These valves help prevent over-pressurization in the system by releasing excess pressure. This ensures that the system operates within safe pressure limits, protecting components from damage. For example, if a surge in water pressure occurs, the relief valve releases the excess to prevent pipe bursts.
  • Variable Frequency Drives (VFDs): VFDs can be used with jockey pumps to control the pump’s speed based on real-time pressure requirements. This allows for more precise pressure maintenance and energy efficiency, as the pump adjusts its operation to match the system’s needs. For instance, in a large commercial building, VFDs help reduce energy consumption by adjusting pump speeds according to demand.

Integration with Fire Protection Systems

Both fire pumps and jockey pumps are integrated into the overall fire protection system, ensuring coordinated operation and optimal performance.

  • System Controllers: Centralized controllers manage the operation of both fire and jockey pumps, ensuring they work together seamlessly. These controllers monitor system conditions and coordinate the activation of pumps based on pressure levels and flow requirements. For example, in an industrial facility, the system controller ensures that both pumps operate in sync to maintain adequate water supply.
  • Alarm Systems: Integrated alarm systems alert operators to any issues with the pumps, such as low pressure, pump failure, or maintenance needs. These alarms ensure that any problems are promptly addressed, maintaining the system’s readiness. Audible and visual alarms provide immediate notification of any system faults.
  • Testing and Monitoring: Regular testing and monitoring are facilitated by the control mechanisms, ensuring that both fire and jockey pumps are in optimal working condition. Automated test cycles can be programmed into the control systems to verify pump functionality and identify potential issues before they become critical. Scheduled tests can include weekly or monthly checks to ensure reliability.

Redundancy and Reliability

Ensuring redundancy and reliability in the control mechanisms of fire pumps and jockey pumps is crucial for the overall effectiveness of the fire protection system.

  • Backup Systems: Redundant control systems and power supplies are often installed to ensure that the pumps operate even if the primary controls fail. This includes backup batteries or generators for electrically powered pumps. For instance, a hospital may have a backup generator to ensure fire pump operation during power outages.
  • Regular Maintenance: Scheduled maintenance and testing are vital to ensure that control mechanisms function correctly. This includes inspecting and calibrating pressure switches, testing control panels, and verifying the operation of manual controls. Routine maintenance activities can prevent unexpected failures and extend the lifespan of the equipment.

By employing advanced control mechanisms, fire protection systems ensure the reliable and efficient operation of fire pumps and jockey pumps. These mechanisms maintain system pressure, coordinate pump activation, and provide alerts for any issues, ensuring the system’s readiness to respond to emergencies effectively.

Function in the System

Introduction

Fire protection systems are crucial for safeguarding lives and property against fire hazards. This chapter explores the essential roles of fire pumps and jockey pumps in these systems, highlighting their functions, integration, and practical applications.

Role of Fire Pumps in Fire Protection Systems

Fire pumps form the backbone of fire protection systems, providing the necessary water supply to combat fires effectively. Their primary function is to deliver high-pressure water to firefighting equipment such as sprinklers, fire hydrants, and hoses during emergencies. This ensures that enough water reaches all parts of a building, especially in high-rise structures where gravity can impede water flow.

Emergency Water Supply

When a fire is detected and firefighting equipment is activated, a significant drop in system pressure occurs. This pressure drop triggers the fire pump to start, ensuring a continuous and powerful water flow to extinguish the fire. For instance, in a multi-story office building, the fire pump ensures that water can reach the upper floors with sufficient pressure to operate sprinklers and hose reels effectively.

Role of Jockey Pumps in Fire Protection Systems

Jockey pumps, also known as pressure maintenance pumps, play a crucial role in maintaining the integrity of the fire protection system during non-emergency conditions. They are designed to maintain system pressure by compensating for minor pressure losses due to leaks, temperature fluctuations, or other factors. By doing so, jockey pumps prevent the fire pump from activating unnecessarily, which helps reduce wear and tear and extends the lifespan of the fire pump.

Pressure Maintenance

Jockey pumps ensure that the fire protection system remains pressurized at all times, ready to respond instantly in case of a fire. They operate intermittently, starting and stopping based on the system’s pressure levels, as monitored by pressure switches. This constant pressure maintenance helps avoid water hammer effects, which are sudden pressure surges that can damage pipes, and short cycling, where pumps frequently turn on and off, leading to wear and tear.

Integration and Coordination

The integration and coordination between fire pumps and jockey pumps are vital for the overall effectiveness of the fire protection system. While the fire pump provides the necessary water supply during emergencies, the jockey pump ensures that the system remains pressurized and ready for immediate activation.

System Readiness

By maintaining consistent pressure, jockey pumps ensure that the fire protection system is always in a state of readiness. This means that when a fire occurs, the system can respond without delay, as the fire pump can immediately take over and deliver the required water flow. This seamless integration between the two pumps is crucial for the reliability and efficiency of the fire protection system.

Redundancy and Reliability

Both fire pumps and jockey pumps are equipped with control mechanisms that ensure their reliable operation. These mechanisms include pressure switches, control panels, and flow switches that monitor and manage the pumps’ performance. Regular testing and maintenance of these control systems are essential to ensure that both pumps function correctly when needed, providing redundancy and reliability in fire protection.

Practical Applications

In various settings, the combined function of fire pumps and jockey pumps ensures optimal fire protection. For example:

  • Commercial Buildings: In high-rise office buildings, jockey pumps maintain system pressure, while fire pumps provide high-pressure water to upper floors during emergencies. For instance, in a real-life scenario where a fire breaks out on the 15th floor, the jockey pump would have kept the system pressurized, allowing the fire pump to immediately supply water to the sprinklers and hoses on that floor.
  • Industrial Facilities: Factories and warehouses benefit from jockey pumps that keep the system pressurized, ready to supply water through fire pumps when a fire breaks out. Imagine a large warehouse with multiple storage levels; the jockey pump ensures the system is pressurized, so the fire pump can quickly deliver water across all levels in the event of a fire.
  • Residential Complexes: Large apartment complexes rely on jockey pumps for pressure maintenance, ensuring that fire pumps can deliver water to all units quickly during a fire. For example, in a sprawling apartment complex, the jockey pump maintains pressure in the system, enabling the fire pump to rapidly distribute water to every unit when a fire alarm is triggered.

By understanding and implementing the distinct but complementary functions of fire pumps and jockey pumps, fire protection systems can achieve maximum effectiveness and reliability, safeguarding lives and property against fire hazards.

Frequently Asked Questions

Below are answers to some frequently asked questions:

What triggers the activation of a fire pump?

The activation of a fire pump is primarily triggered by a significant drop in water pressure within the fire sprinkler system. This drop in pressure can occur due to several factors:

  1. Sprinkler Activation: When a fire sprinkler head activates in response to heat, it releases water, causing a drop in the system’s water pressure. If multiple sprinkler heads are activated, the cumulative effect can reduce the pressure significantly enough to trigger the fire pump.

  2. Small Leaks or System Demands: Minor leaks or pressure fluctuations during maintenance or testing can cause a slight drop in pressure. Initially, the jockey pump, a smaller pump, will activate to maintain system pressure. However, if the pressure drop is more substantial, it can lead to the activation of the main fire pump.

  3. Activation Sequence: The sequence of activation typically starts with the jockey pump, which compensates for minor drops in pressure. If the pressure drop exceeds the jockey pump’s capacity, the main fire pump is activated. This usually happens when there is a significant pressure drop, such as when multiple sprinkler heads are activated. The main fire pump is set to activate upon a predetermined pressure loss, usually around a 5 psi drop from the jockey pump’s activation pressure.

  4. Delayed Turn Off: To avoid the fire pump cycling on and off due to small leaks or intermittent pressure drops, a delay is built into the system. This ensures the pump remains on for a short period after activation, even if the pressure temporarily returns to normal.

In summary, a fire pump is activated by a noticeable drop in water pressure within the sprinkler system, caused by the activation of sprinkler heads, small leaks, or other system demands. The jockey pump helps maintain pressure for minor drops, while the main fire pump handles significant pressure reductions.

How often should a jockey pump operate?

A jockey pump should operate intermittently to maintain the water pressure within a fire protection system. It automatically starts when the pressure drops below a certain threshold and stops once the desired pressure is restored. The jockey pump is designed to handle small flow rates and operates at a higher pressure than the main fire pump to prevent unnecessary activation of the main pump.

Under normal conditions, the jockey pump should not run continuously. Instead, it should start and stop periodically to account for minor pressure drops or leaks in the system. Continuous operation or frequent starts, such as every 30 minutes, generally indicate a potential issue, such as a leak in the system components like drain valves or backflow prevention valves.

To ensure optimal performance and compliance with standards like NFPA 20 and UNE 23.500:2021, the jockey pump should be designed to minimize starts and stops. For example, the UNE 23.500:2021 standard specifies a delay of 10 to 20 seconds for the pump to stop after receiving the stop order from the pressure sensor to reduce frequent cycling.

In summary, a jockey pump should operate intermittently, and frequent or continuous operation usually signals a need for system inspection to identify and repair any leaks or other issues.

Can a fire protection system function without a jockey pump?

A fire protection system can technically operate without a jockey pump, but this would compromise several critical aspects of its functionality and reliability. Jockey pumps are crucial for maintaining consistent water pressure during non-emergency periods, compensating for small leaks or pressure losses to prevent unnecessary cycling of the main fire pump. This helps to maintain system integrity and prevent excessive wear and tear on the main pump, which is not designed for frequent starts and stops.

Without a jockey pump, small leaks could cause continuous starts and stops of the main fire pump, leading to increased maintenance needs and potential premature failure. Moreover, jockey pumps ensure that the fire protection system remains pressurized and ready for emergencies, preventing delays in the activation of sprinklers or other firefighting equipment. The absence of a jockey pump could result in reduced system reliability and increased risk of system failures during a fire.

Additionally, while jockey pumps are not always mandatory, they are recommended by standards such as NFPA 20 to maintain constant pressurization. Not having a jockey pump could lead to non-compliance with these standards, potentially resulting in fines or other penalties.

In conclusion, although a fire protection system can function without a jockey pump in the short term, the long-term reliability, efficiency, and effectiveness of the system would be significantly compromised. The installation of a jockey pump is highly recommended to ensure optimal system performance and compliance with fire safety standards.

What are the maintenance requirements for fire pumps and jockey pumps?

The maintenance requirements for fire pumps and jockey pumps are crucial to ensure the reliability and effectiveness of fire protection systems. Here are the key points:

For fire pumps, weekly inspections include performing a no-flow start and run test for 30 minutes for diesel-driven pumps and 10 minutes for electric pumps. During these inspections, check the pump house temperature, ensure ventilating louvers are functioning properly, and verify that the room is free of combustible materials. Inspect the pump system components such as fuel tank levels, controller settings, battery voltage, and engine oil levels.

Monthly inspections involve performing a flow test to ensure the pump provides the required pressure and flow, inspecting and cleaning the pump strainer, checking the pump’s alignment and coupling, and testing the battery’s voltage and specific gravity.

Annual inspections and tests require a full flow test for both diesel and electric pumps to measure performance at various flow outputs, including 100% and 150% of the rated capacity. This should be conducted by a certified professional. Test pump alarms for pump running, power failure, and valve tamper quarterly, and ensure alarm functions are working correctly with the central station. Inspect and lubricate pump bearings and coupling, and check gauge and pressure switch accuracy.

General maintenance includes servicing hydraulic systems, mechanical transmission, and motor annually. Follow the manufacturer’s recommendations for other tasks, ensuring all valves are fully open, piping is leak-free, and the suction line pressure gauge is accurate.

For jockey pumps, which maintain water pressure in the system, regular checks for leaks and proper operation are essential. The jockey pump should shut off at "pump churn" pressure plus the minimum static pressure on the suction side and start at approximately 10 psi less than the shut-off pressure. The main fire pump should cut in about 5 psi less than the jockey pump start pressure and cut out at the same shut-off pressure.

Regularly include the jockey pump in the inspection and testing schedule to ensure it functions correctly and prevents unnecessary starts of the main fire pump. Proper maintenance of the pressure relief valve associated with the jockey pump is also necessary.

Ensure that all inspections, testing, and maintenance are performed by qualified personnel with the necessary training and experience, as some states require certification for individuals conducting annual fire pump tests. Keep a detailed maintenance log to track inspections, maintenance, and repairs, helping identify recurring issues and ensuring the system is always ready for an emergency. By adhering to these guidelines, largely based on standards from the National Fire Protection Association (NFPA) and other relevant standards, you can maintain optimal conditions for your fire pump and jockey pump systems.

What happens if a jockey pump fails during normal operation?

If a jockey pump fails during normal operation, several critical issues can arise, impacting the overall effectiveness and reliability of the fire protection system.

The primary function of a jockey pump is to maintain the pressure in the firewater header within a specified range. If the jockey pump fails, the pressure in the header will drop below the set point, potentially triggering the main fire pump to start. For instance, if the set point is 150 psig and the jockey pump kick-in pressure is 140 psig, the failure of the jockey pump would result in the pressure falling below 140 psig, which could lead to the main fire pump activation.

In the absence of a functioning jockey pump, the main fire pump may be activated to maintain the required pressure. This is because the main fire pump is designed to start if the pressure in the firewater header falls below a certain threshold. If the jockey pump loses power or fails, the main fire pump will start to restore the necessary pressure to the system.

The failure of a jockey pump can lead to inadequate water pressure in the fire protection system, which is critical during a fire emergency. Without the jockey pump maintaining the pressure, fire sprinklers and hoses may not deliver sufficient water to effectively combat the fire, resulting in delayed fire suppression and increased risk to life and property.

Fire pumps, including jockey pumps, are mandated by building and fire codes. If a jockey pump fails to operate, it could lead to code violations, fines, or even legal action, as the entire fire protection system could be compromised.

In the event of a jockey pump failure, it is crucial to take immediate action. This includes stopping all operations and potentially evacuating the facility if occupied, contacting a fire protection services company for a comprehensive inspection and necessary repairs or replacements, and testing the fire pump system post-maintenance to ensure the issue is resolved and the system operates correctly.

Regular maintenance, inspections, and testing are essential to prevent jockey pump failures. Monitoring the operational status of the pump, checking for signs of wear and tear, and addressing any issues promptly can help ensure the pump’s reliability and the overall effectiveness of the fire protection system.